2530 Motorised Fire Damper

2530 Fire & Smoke Damper

The Advanced Air 2530 Motorised Fire Damper is designed to meet the requirements of dynamic fire testing, offering low leakage at ambient and high temperatures during the fire test. Its main purpose is to close on alarm activation and to stay closed, maintaining the integrity of the fire-rated barrier and stopping the spread of fire, cold, and hot smoke, including toxic fumes.

The 2530 incorporates a blade profile of aerodynamic double skin construction with a metal-to-metal seal, interlocking opposed operation, achieving low leakage for smoke performance as stipulated in BS EN1366-2 with a classification of two hours in both horizontal and vertical installations.

The 2530 includes a unique and versatile jackshaft arrangement with an electrical thermal fuse rated at 74 °C. When reached the actuator power is disengaged, the actuator closes the blades within 15 seconds. The blades are then held in the closed position by the knee-lock mechanism, therefore not relying on the actuator to hold the blades closed. When actuator power is restored, the damper opens within 90 seconds. The 2530 Motorised Fire Damper is available with spigotted connections.

Various tested installation options are available and are detailed in our Installation, Operation and Maintenance manual. This product is both flexible and versatile and can be modified to meet most special requirements on size and installation.

Advanced Air also offers training on how to install the products correctly within our in-house training facility. Installation Training

Description of Image

Description of Image

Description of Image

Description of Image

Description of Image

Description of Image

 
 
 
 
 

Features

  • Complies with BS EN 15650
  • Tested in both directions to BS EN 1366-2
  • ES 120 classification to BS EN 13501-3
  • Tested for both vertical and horizontal installation
  • 15 second closing, 90 second opening
  • Junction box for power connection
  • Easy AFS Installation
  • Modulating option for volume control
  • Stainless Steel 430 option

Tech Specs

Blades Opposed blades, double skinned
Width 135mm standard
Centres 125mm
Material  1.0mm Galvanised Mild Steel – Standard
1.0mm Grade 430 Stainless Steel – Optional

Case
Case depth  Default 113mm – with 150mm spigot and 75mm spigot as standard. (75mm spigot will increase when single blade damper are manufactured, see product drawings)
Should access doors be required to be fitted the 150mm spigot will increase to 225mm.

For existing/current projects the dampers will continue to be supplied with either a 125mm/250mm and 50mm spigots.

Units with a duct size under 200mm, circular and flat oval spigotted units will be supplied with additional step down spigots.

Material 1.2mm Galvanised – Standard
1.2mm Grade 430 Stainless Steel – Optional

Corners Welded mitre corners finished with aluminium aerosol spray.
Linkage External, Zinc electroplated mild steel enclosed with the frame, out of air stream, fixed for 90 degree operation – Standard
Bearings  12.7mm diam. Oil Filled Sintered Bronze suitable for use up to 200°C – Standard
12.7mm diam. Stainless Steel suitable for use up to 650°C – Optional

Axles  12.7mm diam. Zinc Electroplated Mild Steel bolted directly through blade
Jackshaft    12.7mm diameter zinc electroplated mild steel
Side Jamb Seals Stainless Steel Grade 301 S21 – to BSEN10088-2 1.4310 – cambered profile
Top & Bottom Jambs Seals Stainless Steel Grade 301 S21 – to BSEN10088-2 1.4310 – cambered profile
Environment  These units are not suitable for installation with a corrosive or hostile environment or an area of high humidity

Dimensions

Duct Size (Single section)  – THIS IS CE CERTIFIED
Rectangular Minimum 100mm wide x 100mm high (Case size 250mm x 250mm)
Maximum Single Section 1000mm wide x 1000mm high

Circular Minimum 100mm diameter (case size 250 x 250)
Maximum 950mm diameter

Flat Oval Minimum 100mm wide x 100mm high (Case size 250mm x 250mm)
Maximum 950mm on the longest dimension.

Duct size (multi-section shipped as one piece): THIS IS CE CERTIFIED
Rectangular: Maximum multi-section 2000mm wide x 2000mm high.
Circular: 1500mm diameter
Flat Oval: Maximum 1500mm on the longest dimension
Duct size (multi-section shipped in separate sections): THESE ARE NOT CE CERTIFIED
Rectangular: For sizes above 2000mm x 2000mm, further structural support may be required; please consult a Structural Engineer for advice.
Circular: Not available.
Flat Oval: Not available.

Tested Wall Types

wdt_ID wdt_created_by wdt_created_at wdt_last_edited_by wdt_last_edited_at Damper Type Model Install Construction Wall Build Up Wall Rating Min Depth Max Size Test Classification
1 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 11:26 AM Fire Damper 0160/AFWA Wall Drywall 2x15mm layers each side EN520 F-Type Board 120 mins 131mm 1,000 x 1,000mm EN1366-2 E120 (Ve io)
2 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160/AFWA Wall Rigid Wall Concrete/Blockwork 120 mins 131mm 1,000 x 1,000mm EN1366-2 E120 (Ve io)
3 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160/AFWA/Multi Unit Wall Drywall 2x15mm layers each side EN520 F-Type Board 120 mins 136mm 2,000 x 2,000mm EN1366-2 E120 (Ve io)
4 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160/AFWA/Multi Unit Wall Rigid Wall Concrete/Blockwork 120 mins 136mm 2,000 x 2,000mm EN1366-2 E120 (Ve io)
5 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160/AFWA Wall Drywall 2x12.5mm layers each side EN520 F-type board 60 mins 94mm 1,000 x 1,000mm EN1366-2 E60 (Ve io)
6 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160/AFWA Wall Rigid Wall Concrete/Blockwork 60 mins 94mm 1,000 x 1,000mm EN1366-2 E60 (Ve io)
7 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160/AFWA Wall Shaft Wall Shaft Wall British Gypsum 1X19mm coreboard shaft side, 3x15mm f-Type EN520 board non-shaft side 120 mins 117mm 1,000 x 1,000mm EN1366-2 E120 (Ve io)
8 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160/HVF Wall Rigid Wall Concrete/Blockwork 120 mins 150mm 1,000 x 1,000mm EN1366-2 E120 (Ve io)
9 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160 DFC Wall Drywall 2x15mm layers each side EN520 F-Type Board 120 mins 122mm 1,000 x 1,000mm EN1366-2 E120 (Ve io)
10 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160 AFFL Floor Floor Concrete slab 120 mins 150mm 1,000 x 1,000mm EN1366-2 E120 (Ho i<-)
11 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160 HVF Floor Floor Concrete slab 120 mins 150mm 1,000 x 1,000mm EN1366-2 E120 (Ho io)
12 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160 AFWA Wall Shaft Wall Shaft Wall Siniat 1X19mm coreboard shaft side, 2x12.5mm EN520 F-Type board non-shaft side 60 mins 85mm 1,000 x 1,000mm EN1366-2 E90 (Ve io)
13 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160 Trimo Wall Shaft Wall TrimoTerm 120 mins 120mm 1,000 x 1,000mm EN1366-2 E120 (Ve io)
14 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0160 AFWA Wall Drywall Group A 90 minute flexible supporting construction to BS EN 1363-1. 2x layers of 12.5mm Type F plasterboard either side of stud. 90 mins 94mm 1,000 x 1,000mm EN1366-2 E90 (Ve io)
15 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0400 MAN Wall Drywall 2x15mm layers each side EN520 F-Type Board 120 mins 131mm ⌀315mm EN1366-2 E120 (Ve io)
16 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0400 MAN Wall Rigid Wall Concrete/Blockwork 120 mins 131mm ⌀315mm EN1366-2 E120 (Ve io)
17 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0400 MAN Wall Drywall 2x12.5mm layers each side EN520 F-type board 60 mins 106mm ⌀315mm EN1366-2 E60 (Ve io)
18 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0400 MAN Wall Rigid Wall Concrete/Blockwork 60 mins 106mm ⌀315mm EN1366-2 E120 (Ho i<-o)
19 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Fire Damper 0500 MAN Floor Floor Concrete slab 120 mins 150mm ⌀315mm EN1366-2 E120 (Ho i<-o)
20 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 2530 AFWA Wall Drywall 2x15mm layers each side EN520 F-Type Board 120 mins 122mm 1,000 x 1,000mm EN1366-2 E120 (Ve io)s
21 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 2530 AFWA Wall Rigid Wall Concrete/Blockwork 120 mins 122mm 1,000 x 1,000mm EN1366-2 E120 (Ve io)s
22 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 2530 AFWA Multi Unit Wall Drywall 2x15mm layers each side EN520 F-Type Board 120 mins 150mm 2,000 x 2,000mm EN1366-2 E120 (Ve io)s
23 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 2530 AFWA Multi Unit Wall Rigid Wall Concrete/Blockwork 120 mins 150mm 2,000 x 2,000mm EN1366-2 E120 (Ve io)s
24 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 2530 AFWA Wall Drywall 2x12.5mm layers each side EN520 F-type board 60 mins 94mm 1,000 x 1,000mm EN1366-2 E90 (Ve io)s
25 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 2530 AFWA Wall Rigid Wall Concrete/Blockwork 60 mins 94mm 1,000 x 1,000mm EN1366-2 E90 (Ve io)s
26 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 2530 AFWA Wall Shaft Wall Shaft Wall British Gypsum 1X19mm coreboard shaft side, 3x15mm f-Type EN520 board non-shaft side 120 mins 107mm 1,000 x 1,000mm EN1366-2 E120 (Ve io)s
27 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 2530 AFFL Floor Floor Concrete Upstand 120 mins 150mm Upstand 1,000 x 1,000mm EN1366-2 E120 (Ho i<-o)s
28 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 2530 AFFL Floor Floor Concrete slab 120 mins 150mm 1,000 x 1,000mm EN1366-2 E120 (Ho i<-o)s
29 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 2530 HVF Floor Floor Concrete slab 120 mins 150mm 1,000 x 1,000mm EN1366-2 E120 (Ho io)s
31 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 2530 Trimo Wall Shaft Wall TrimoTerm 120 mins 120mm 1,000 x 1,000mm EN1366-2 E120 (Ve io), E90 (Ve io)s
32 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 0400 FME Wall Drywall 2x15mm layers each side EN520 F-Type Board 120 mins 131mm ⌀315mm EN1366-2 E120 (Ve io)s
33 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 0400 FME Wall Rigid Wall Concrete/Blockwork 120 mins 131mm ⌀315mm EN1366-2 E120 (Ve io)s
34 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 0400 FME Wall Drywall 2x12.5mm layers each side EN520 F-type board 60 mins 106mm ⌀315mm EN1366-2 E60 (Ve io)s
35 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 0400 FME Wall Rigid Wall Concrete/Blockwork 60 mins 106mm ⌀315mm EN1366-2 E60 (Ve io)s
36 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Motorised Fire Damper 0500 FME Floor Floor Concrete slab 120 mins 150mm ⌀315mm EN1366-2 E120 (Ho i<-o)s
37 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Smoke Control Dampers 26SCD AFWA Wall Drywall 2x15mm layers each side EN520 F-Type Board 120 mins 122mm 1,000 x 1,000mm EN1366-10 E120 (Vew io)S500 C10000(Cmod)/Multi
38 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Smoke Control Dampers 26SCD AFWA Wall Rigid Wall Concrete/Blockwork 120 mins 122mm 1,000 x 1,000mm EN1366-10 E120 (Vew io)S500 C10000(Cmod)/Multi
40 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Smoke Control Dampers 26SCD/HP AFWA 1000Pa Wall Drywall 2x15mm layers each side EN520 F-Type Board 120 mins 122mm 1,000 x 1,000mm EN1366-10 E120 (Vew io)S1000 C10000(Cmod)/Multi
41 IT__admin 28/04/2025 10:01 AM IT__admin 28/04/2025 10:01 AM Smoke Control Dampers 26SCD/HP AFWA 1000Pa Wall Rigid Wall Concrete/Blockwork 120 mins 122mm 1,000 x 1,000mm EN1366-10 E120 (Vew io)S1000 C10000(Cmod)/Multi
Damper Type Install Construction Wall Rating
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.

Strictly Necessary Cookies

Strictly Necessary Cookie should be enabled at all times so that we can save your preferences for cookie settings.

3rd Party Cookies

This website uses Google Analytics to collect anonymous information such as the number of visitors to the site, and the most popular pages.

Keeping this cookie enabled helps us to improve our website.